How many strength test sets and cylinders a pour requires, and whether the results that came back satisfy the acceptance criteria.
The code counts each day's placing on its own; over several days the totals give the least it can need. Use Day by day for the exact count.
Everything you have entered is in the address bar, so the link reproduces this exact calculation.
One row per strength test: the cylinders from one sample, at least two 6 × 12 in (150 × 300 mm) or three 4 × 8 in (100 × 200 mm).
| Test | 1 | 2 | 3 | Avg |
|---|---|---|---|---|
| 1 | 4167 | |||
| 2 | 3883 | |||
| 3 | 4283 | |||
| 4 | 3750 | |||
| 5 | 4450 | |||
| 6 | 4117 | |||
| 7 | 3650 | |||
| 8 | 4250 | |||
| 9 | 4017 | |||
| 10 | 4417 |
| Check | Demand | Capacity | DCR | Status |
|---|---|---|---|---|
| Test 1 — individual strength | 3500 psi | 4167 psi | 0.840 | ✓ OK |
| Test 2 — individual strength | 3500 psi | 3883 psi | 0.901 | ✓ OK |
| Test 3 — individual strength | 3500 psi | 4283 psi | 0.817 | ✓ OK |
| Tests 1–3 — running average | 4000 psi | 4111 psi | 0.973 | ✓ OK |
| Test 4 — individual strength | 3500 psi | 3750 psi | 0.933 | ✓ OK |
| Tests 2–4 — running average | 4000 psi | 3972 psi | 1.007 | ✗ FAIL |
| Test 5 — individual strength | 3500 psi | 4450 psi | 0.787 | ✓ OK |
| Tests 3–5 — running average | 4000 psi | 4161 psi | 0.961 | ✓ OK |
| Test 6 — individual strength | 3500 psi | 4117 psi | 0.850 | ✓ OK |
| Tests 4–6 — running average | 4000 psi | 4106 psi | 0.974 | ✓ OK |
| Test 7 — individual strength | 3500 psi | 3650 psi | 0.959 | ✓ OK |
| Tests 5–7 — running average | 4000 psi | 4072 psi | 0.982 | ✓ OK |
| Test 8 — individual strength | 3500 psi | 4250 psi | 0.824 | ✓ OK |
| Tests 6–8 — running average | 4000 psi | 4006 psi | 0.999 | ✓ OK |
| Test 9 — individual strength | 3500 psi | 4017 psi | 0.871 | ✓ OK |
| Tests 7–9 — running average | 4000 psi | 3972 psi | 1.007 | ✗ FAIL |
| Test 10 — individual strength | 3500 psi | 4417 psi | 0.792 | ✓ OK |
| Tests 8–10 — running average | 4000 psi | 4228 psi | 0.946 | ✓ OK |
A thin element can cover a large area on very little concrete, which the volume criterion alone would under-test.
The calculated criteria give 3; the ACI 318-08 minimum of 5 governs.
Results are for preliminary sizing and educational use. They are not a design and must be reviewed, verified and sealed by a licensed or registered engineer before being used in construction.
concrete-test-cylinder v1.2.0 · ACI 318-08 · input c705f39e792c32f2